Plan Review Notes
Plan Review Notes For Permit 02041748
Permit Number 02041748
Review Stop E
Sequence Number 2
Notes
Date Text
2002-08-22 00:00:00************ UNSAT ******************
  
 1)NOTE: PLEASE NOTE A REVISED RISER
 DIAGRAM IS SUBMITTED. PLEASE NOTE THAT
 AIC RATINGS FOR MAIN AND PANELS ARE
 NOT SUBMITTED. IT IS NOTED THAT BRKRS
 ARE TO BE RATED FOR MAX, BUT NO RATING
 ACTUALLY SHOWN. 110-9/215-5
  
 2)NOTE: PLEASE NOTE THAT NOT ALL NOTES
 FROM FIRST REVIEW WERE ADDRESSED.
  
 3)NOTE: PLEASE NOTE WIRE SIZES ARE NOT
 SHOWN ON PANEL SCHEDULES.?
  
 4)NOTE: PLEASE NOTE, RISER DIAGRAM
 SHOWS PANEL "S" BEING IN SPACE 102 AND
 YET IS STILL SHOWN IN SPACE 104 ON E-1?
 PLEASE CLARFIY. E-2 DOES NOT SHOW IN
 THIS SPACE?
  
 5)NOTE: PLEASE NOTE, LOAD CALCULATIONS
 WERE NOT SUBBITTED. PLEASE SHOW WATTS/
 SQ.FT, RECEPTS..180VA EACH, PLEASE
 SHOW ALL CONTINUOUS LOADS AT 125%.
 215-5,220-3,220-10,220-11,220-13,230-42
 215-3.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372