2002-08-22 00:00:00 | ************ UNSAT ****************** | | | | 1)NOTE: PLEASE NOTE A REVISED RISER | | DIAGRAM IS SUBMITTED. PLEASE NOTE THAT | | AIC RATINGS FOR MAIN AND PANELS ARE | | NOT SUBMITTED. IT IS NOTED THAT BRKRS | | ARE TO BE RATED FOR MAX, BUT NO RATING | | ACTUALLY SHOWN. 110-9/215-5 | | | | 2)NOTE: PLEASE NOTE THAT NOT ALL NOTES | | FROM FIRST REVIEW WERE ADDRESSED. | | | | 3)NOTE: PLEASE NOTE WIRE SIZES ARE NOT | | SHOWN ON PANEL SCHEDULES.? | | | | 4)NOTE: PLEASE NOTE, RISER DIAGRAM | | SHOWS PANEL "S" BEING IN SPACE 102 AND | | YET IS STILL SHOWN IN SPACE 104 ON E-1? | | PLEASE CLARFIY. E-2 DOES NOT SHOW IN | | THIS SPACE? | | | | 5)NOTE: PLEASE NOTE, LOAD CALCULATIONS | | WERE NOT SUBBITTED. PLEASE SHOW WATTS/ | | SQ.FT, RECEPTS..180VA EACH, PLEASE | | SHOW ALL CONTINUOUS LOADS AT 125%. | | 215-5,220-3,220-10,220-11,220-13,230-42 | | 215-3. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|