Plan Review Notes For Permit 02041746 |
Permit Number |
02041746 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-05-18 00:00:00 | DENIED | | REFERENCE: FBC-2001 CHAPTER 11 | | FBC-2001 PLUMBING | | | | 1) SHT A-3 SAMPLE POINT SHALL BE FOR | | GREASE WASTE ONLY. SEPARATE 3-COMPART- | | MENT SINK, FLOOR DRAIN, AND MOP SINK | | THEN INSTALL SAMPLE POINT. AFTER SAMPLE | | POINT THEN TIE INTO SANITARY | | 2) SHT A-3 SANITARY RISER DIAGRAM SHALL | | REFLECT THE FLOOR PLAN, TOILET ROOMS DO | | NOT TIE IN AFTER 3-COMP SINK ECT. | | 3) SHT A-3 HUB DRAIN NOT APPROVED FOR | | INDIRECT WASTE. (ICE/SODA MACHINE) FLOOR | | SINK REQUIRED FOR ALL INDIRECT WASTE. | | SEC 802.3 | | 4) SHT A-3 WATER FILTRATION SYSTEM FOR | | ICE MACHINE SHALL BE NSF APPROVED. | | PLEASE PROVIDE MANUFACTURE INFORMATION. | | 5) SHT A-3 DRINKING FOUNTAIN REQUIRED | | TABLE 403.1. ALSO SEE 410.1 BOTTLED | | WATER REQUIREMENT ARI-1010 IF USED SUB- | | MIT MANUF. INFO SHOWING COMPLIANCE. | | 6) SHT A-3 TOILET ROOM ELEVATIONS, URNAL | | SHALL BE 17" TO LIP AFF MAX. | | 7) SHT A-3 WATER RISER DIAGRAM, AIR | | CHAMBERS NOT APPROVED (NOTE #4). | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|