Plan Review Notes
Plan Review Notes For Permit 02041746
Permit Number 02041746
Review Stop P
Sequence Number 1
Notes
Date Text
2002-05-18 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) SHT A-3 SAMPLE POINT SHALL BE FOR
 GREASE WASTE ONLY. SEPARATE 3-COMPART-
 MENT SINK, FLOOR DRAIN, AND MOP SINK
 THEN INSTALL SAMPLE POINT. AFTER SAMPLE
 POINT THEN TIE INTO SANITARY
 2) SHT A-3 SANITARY RISER DIAGRAM SHALL
 REFLECT THE FLOOR PLAN, TOILET ROOMS DO
 NOT TIE IN AFTER 3-COMP SINK ECT.
 3) SHT A-3 HUB DRAIN NOT APPROVED FOR
 INDIRECT WASTE. (ICE/SODA MACHINE) FLOOR
 SINK REQUIRED FOR ALL INDIRECT WASTE.
 SEC 802.3
 4) SHT A-3 WATER FILTRATION SYSTEM FOR
 ICE MACHINE SHALL BE NSF APPROVED.
 PLEASE PROVIDE MANUFACTURE INFORMATION.
 5) SHT A-3 DRINKING FOUNTAIN REQUIRED
 TABLE 403.1. ALSO SEE 410.1 BOTTLED
 WATER REQUIREMENT ARI-1010 IF USED SUB-
 MIT MANUF. INFO SHOWING COMPLIANCE.
 6) SHT A-3 TOILET ROOM ELEVATIONS, URNAL
 SHALL BE 17" TO LIP AFF MAX.
 7) SHT A-3 WATER RISER DIAGRAM, AIR
 CHAMBERS NOT APPROVED (NOTE #4).
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377