2002-05-17 00:00:00 | UNSAT! | | ~~~~~~ | | 1} PLEASE NOTE THE CONDUCTORS ON THE | | PANEL SCHEDULE FOR THE DRYER ARE SHOWN | | AS #12 ON A 30AMP CIRCUIT | | BREAKER,SERVING A 5KW LOAD.PLEASE | | CORRECT. | | | | 2} THE ARCHITECTS TITLE BLOCK IS NOT | | SEALED ON THE PLANS PER FS/FAC 481-221. | | | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | 561/659-8096 EXT. 8392 |
|