2002-05-17 00:00:00UNSAT!
 ~~~~~~
 1} PLEASE NOTE THE CONDUCTORS ON THE
 PANEL SCHEDULE FOR THE DRYER ARE SHOWN
 AS #12 ON A 30AMP CIRCUIT
 BREAKER,SERVING A 5KW LOAD.PLEASE
 CORRECT.
  
 2} THE ARCHITECTS TITLE BLOCK IS NOT
 SEALED ON THE PLANS PER FS/FAC 481-221.
  
  