Plan Review Notes
Plan Review Notes For Permit 02041671
Permit Number 02041671
Review Stop R
Sequence Number 1
Notes
Date Text
2002-06-10 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) THE AREA OF THE WALL OPENINGS AT THE
 FRONT ELEVATION EXCEEDS THE PERCENTAGE
 ALLOWED BY TABLE 600. THE CALCULATIONS
 ARE INCORRECT. THE PERCENTAGE ALLOWED IS
 20% FROM OVER 3 FEET TO 10 FEET AND IS
 40% FROM OVER 10 FEET TO 20 FEET. PLEASE
 CORRECT.
  
 3) THE 2001 FBC SECTION 1606.1.7
 REQUIRES THE FOLLOWING INFORMATION TO BE
 SHOWN ON THE CONSTRUCTION DRAWINGS:
 - BASIC WIND SPEED, MPH.
 - WIND IMPORTANCE FACTOR(1) AND BUILDING
 CATEGORY.
 - WIND EXPOSURE- IF MORE THAN ONE WIND
 EXPOSURE IS USED THE WIND EXPOSURE AND
 APPLICABLE WIND DIRECTION SHALL BE
 INDICATED.
 - THE APPLICABLE INTERNAL PRESSURE
 COEFFICIENT
 - COMPONENTS AND CLADDING. THE DESIGN
 WIND PRESSURES IN TERMS OF PSF, TO BE
 USED FOR THE DESIGN OF EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED
 DESIGN PROFESSIONAL.
 PLEASE UPDATE THE DESIGN INFORMATION ON
 S1.
  
 4) INDICATE THE POSITIVE AND NEGATIVE
 WINDLOAD PRESSURES FOR THE SKYLIGHT AND
 THE 25 SH WINDOW IN THE GARAGE.
  
 5) REVISE NOTE #2 ON A1 TO REFERENCE THE
 FLORIDA BUILDING CODE.
  
 6) REVISE THE BUCK DETAIL #2 ON A4 TO
 COMPLY WITH FBC SEC. 1707.4.4.2.
  
 7) PLEASE UPDATE THE FOLLOWING NOTES ON
 S4 TO REFERENCE THE 2001 FBC:
 - #3 & #4 UNDER GENERAL NOTES
 - #9 UNDER GENERAL NOTES TO ASCE 7-98 &
 140 MPH (3 SEC. GUST)
 - #1 UNDER SAFEGUARDS
 - #1 UNDER REINFORCED CONCRETE
 - #2 UNDER TRUSSES
 - #5 UNDER ROOF SHEATHING
  
 8) PLEASE REVISE NOTE #7, THE CORRECT
 REFERENCE IS ASTM A 185. THE WELDED WIRE
 FABRIC IS REQUIRED TO BE SUPPORTED PER
 FBC SEC. 1909.3.
  
 9) THE NEGATIVE PRESSURE FOR THE 1/2- 36
 SH KDI WINDOWS IN THE DEN AND LIVING
 ROOM EXCEED THE VALUE IN THE SBCCI
 PRODUCT EVALUATION REPORT. THE
 COMPARATIVE ANALYSIS REPORT SUBMITTED IS
 NOT VALID UNLESS IT IS AN ORIGINAL
 SIGNED AND SEALED COPY.
  
 10) PLEASE SUBMIT KEY PLANS AND
 INSTALLATION SCHEDULE FOR THIS MODEL.
  
 11) THE PRODUCT APPROVAL FOR ENTEGRA
 ROOF TILE IS EXPIRED.
  
 12) PROVIDE THE CORRECT GARAGE DOOR
 DRAWING. THE ONE ATTACHED TO THE PRODUCT
 APPROVAL IS FOR A 9 FOOT DOOR.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202