Plan Review Notes
Plan Review Notes For Permit 02041656
Permit Number 02041656
Review Stop R
Sequence Number 1
Notes
Date Text
2002-05-31 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) INDICATE THE POSITIVE AND NEGATIVE
 PRESSURES FOR THE GLASS BLOCK OPENINGS
 AND THE SKYLIGHT ON THE PLANS.
  
 3) PLEASE REVISE DETAIL 2 ON A4 TO SHOW
 BUCKS THAT EXTEND BEYOND THE FACE OF THE
 WINDOW FRAME AND THE FRAME ANCHORS
 THROUGH THE 1X AND INTO THE STRUCTURAL
 SUBSTRATE MATERIAL AS REQUIRED BY FBC
 SEC. 1707.4.4.2.
  
 4) PLEASE UPDATE THE DESIGN CRITERIA ON
 SHEET S1 TO THE 2001 FBC, (ASCE 7-98,
 140 MPH 3 SECOND GUST).
 THE 2001 FBC SECTION 1606.1.7
 REQUIRES THE FOLLOWING INFORMATION TO BE
 SHOWN ON THE CONSTRUCTION DRAWINGS:
 - BASIC WIND SPEED, MPH.
 - WIND IMPORTANCE FACTOR(1) AND BUILDING
 CATEGORY.
 - WIND EXPOSURE- IF MORE THAN ONE WIND
 EXPOSURE IS USED THE WIND EXPOSURE AND
 APPLICABLE WIND DIRECTION SHALL BE
 INDICATED.
 - THE APPLICABLE INTERNAL PRESSURE
 COEFFICIENT
 - COMPONENTS AND CLADDING. THE DESIGN
 WIND PRESSURES IN TERMS OF PSF, TO BE
 USED FOR THE DESIGN OF EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED
 DESIGN PROFESSIONAL.
  
 5) INDICATE ON THE PLANS THAT THE WELDED
 WIRE REINFORCEMENT FABRIC WILL BE
 SUPPORTED WITH APPROVED MATERIALS OR
 SUPPORTS PER THE 2001 FBC SEC. 1909.3.
  
 6) PLEASE REVISE GENERAL NOTES (3) & (4)
 ON S4 FROM THE STANDARD TO THE FLORIDA
 BUILDING CODE. ALSO, REVISE NOTE (9) TO
 ASCE 7-98 (140 MPH) FROM ASCE 7-95 (145
 MPH).
  
 7) PLEASE REVISE DETAIL 4 ON A4 WHICH
 REFERENCES THE STANDARD BUILDING CODE.
  
 8) PLEASE REVIEW AND CORRECT THE WALL
 AREA PERCENTAGE CALCULATIONS ON SHEET A2
 THE LENGTH OF WALL AREA AT 20 PERCENT IS
 33 FEET, WHICH IS ADJACENT TO LOT 46.
  
 9) SBCCI EVALUATION REPORT # 9733 FOR
 KDI HAS BEEN REPLACED BY # 9733A. PLEASE
 SUBMIT THE CURRENT REPORT.
  
 10) THE PRODUCT APPROVAL FOR ENTEGRA
 ROOF TILE EXPIRED ON 10-01-01. PLEASE
 SUBMIT THE CURRENT PRODUCT APPROVAL.
  
 11) THE KEY PLAN AND INSTALLATION
 SCHEDULE SUBMITTED IS FOR A DIFFERENT
 MODEL. PLEASE SUBMIT THE ONES FOR THIS
 MODEL.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202