2002-05-15 00:00:00***************** UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT THE OVEN THAT
 IS SHOWN ON PANEL SCHEDULE IS NOT SHOWN
 ON LOAD CALCUALTIONS. PLEASE CORRELATE.
  
 2)NOTE: PLEASE NOTE A 10KW LOAD SHOWN
 W/ 50A OCP AND #8 AWG. PLEASE SEE 424-3B
  
 3)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTION PER 210-12 ON PANEL SCHEDULE.
  
 4)NOTE: PLEASE CLARIFY, PLANS SAYS
 MAIN DISC NEXT TO METER AND PLANS SHOW
 NEXT TO PANEL INSIDE GARAGE? PLEASE
 CORRELATE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
  
 5)NOTE: PLEASE NOTE THAT GROUNDING
 ELECTRODE CONDUCTOR SIZED PER 250-66
 3/0`S.......