Plan Review Notes For Permit 02041630
Permit Number 02041630
Review Stop E
Sequence Number 3
Notes
Date Text
2002-07-23 00:00:00****************** UNSAT **************
  
 ********** NOTE ************
 3RD TIME UNSAT, PLEASE SEE ATTACHED
 SHEET FOR FS.553.802B. PLANS BEING SENT
 BACK FOR THE SAME COMMENTS.
 PLEASE SEE ATTACHED SHEETS FOR PREVIOUS
 TWO REVIEWS AND COMMENTS.
  
 1)NOTE: PLEASE NOTE AN EQUIPMENT GROUND-
 -ING CONDUCTOR IS STILL BEING SHOWN
 BETWEEN METER AND MAIN?? THIS IS PARA-
 LLELING THE NEUTRAL WHICH IS NOT
 PERMITTED. PLEASE NOTE THAT THE NEUTRAL
 IS BONDED WITH THE GRND SCREW AT THE
 FIRST MEANS OF DISC.
  
 2)NOTE: PLEASE NOTE THAT THE TWO SMALL
 APPLIANCE CIRCUITS REQ`D PER 210-52B
 210-11-C-1 ARE STILL NOT SHOWN IN LOAD
 CALCULATIONS?? PLEASE NOTE MICROWAVE IS
 SHOWN ON LOAD CALCS BUT NOT PANEL
 SCHEDULE?
  
 3)NOTE: PLEASE VERIFY LOAD SHOWN FOR
 RANGE AT 5KW?
  
 4)NOTE: PLEASE NOTE SD IS SHOWN IN BATH,
 SD`S ARE NOT PERMITTED IN BATHS PER
 NFPA-72, 2-5.2.1.6
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW AND
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
  
  
 BILL TROBAUGH
 X-8392