Plan Review Notes For Permit 02041630
Permit Number 02041630
Review Stop R
Sequence Number 2
Notes
Date Text
2002-07-10 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) THE NEGATIVE WINDLOAD PRESSURE GIVEN
 ON THE PLANS (-118.40 PSF ) FOR THE 1/2
 33SH BATHROOM WINDOW,EXCEEDS THE MAXIMUM
 NEGATIVE DESIGN PRESSURE LISTED IN THE
 KDI WINDOW COMPARATIVE ANALYSIS CHART
 FOR THAT SIZE WINDOW (-109 PSF).
 PLEASE CORRECT.
  
 3) THE MAXIMUM SPACING FOR WELDED WIRE
 MESH SUPPORTS SHALL NOT EXCEED 3 FEET OR
 MANUFACTURERS' SPECIFICATIONS PER FBC
 SECTION 1909.3 (2). PLEASE REVISE THE
 NOTES ON SHEETS S1 AND S4 TO REFLECT
 THIS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202