Plan Review Notes
Plan Review Notes For Permit 02041630
Permit Number 02041630
Review Stop E
Sequence Number 2
Notes
Date Text
2002-07-09 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE NOTE THE FOLLOWING
 DISCREPANCIES,CORRECT PLANS AND
 RESUBMIT FOR REVIEW:
  
 1} RISER STILL HAS THE EQUIPMENT GROUND
 FROM THE METER TO THE DISCONNECT.PLEASE
 REMOVE.
  
 2} THE SMALL APPLIANCE CIRCUITS NEED TO
 BE INCLUDED IN THE LOAD CALCULATIONS AS
 INDICATED ON THE PREVIOUS REVIEW.
  
 3} SHEET E-1.0 HAS AN ARCHITECTURAL
 TITLE BLOCK BUT IS NOT SEALED PER
 61G1-16.001 FAC.
  
  
 IF THERE ARE ANY QUESTION PLEASE CALL:
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT. 8392