Plan Review Notes For Permit 02041630 |
Permit Number |
02041630 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2002-07-09 00:00:00 | UNSAT | | ~~~~~ | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | PLEASE NOTE THE FOLLOWING | | DISCREPANCIES,CORRECT PLANS AND | | RESUBMIT FOR REVIEW: | | | | 1} RISER STILL HAS THE EQUIPMENT GROUND | | FROM THE METER TO THE DISCONNECT.PLEASE | | REMOVE. | | | | 2} THE SMALL APPLIANCE CIRCUITS NEED TO | | BE INCLUDED IN THE LOAD CALCULATIONS AS | | INDICATED ON THE PREVIOUS REVIEW. | | | | 3} SHEET E-1.0 HAS AN ARCHITECTURAL | | TITLE BLOCK BUT IS NOT SEALED PER | | 61G1-16.001 FAC. | | | | | | IF THERE ARE ANY QUESTION PLEASE CALL: | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | 561/659-8096 EXT. 8392 |
|