2002-05-15 00:00:00~~~~~~~~~~~~~~~~~UNSAT!~~~~~~~~~~~~~~~~~
 PLEASE NOTE THE FOLLOWING
 DISCREPANCIES,CORRECT PLANS AND
 RESUBMIT FOR REVIEW.
  
 1} THE RISER DIAGRAM INDICATES THE
 EQUIPMENT GROUND BEING RAN FROM THE
 METER TO THE DISCONNECT.PLEASE REMOVE
 SAME TO AVOID A PARALLEL GROUND/NEUTRAL
 PATH.
  
 2} INCLUDE SMALL APPLIANCE CIRCUITS IN
 LOAD CALC. PER 220-30.
  
 3} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE. PER 210-12
  
 4} LIST KITCHEN CIRCUITS ON PANEL
 SCHEDULE.
  
 5} A/C #1 AHU @ 10K,BREAKER AND BRANCH
 CIRCUIT CONDUCTORS ARE UNDERSIZED.
  
 6} THE WASHER IS LISTED AT 3000W IN THE
 LOAD CALCS AND SHOWN ON A 20 AMP BREAKER
 WITH #12 WIRE ON THE PANEL SCHEDULE,
 PLEASE CLARIFY.
  
 7} OVEN SHOWN ON PANEL SCHEDULE, BUT NOT
 IN LOAD CALCS,PLEASE CLARIFY.
  