Plan Review Notes For Permit 02041630 |
Permit Number |
02041630 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-05-15 00:00:00 | ~~~~~~~~~~~~~~~~~UNSAT!~~~~~~~~~~~~~~~~~ | | PLEASE NOTE THE FOLLOWING | | DISCREPANCIES,CORRECT PLANS AND | | RESUBMIT FOR REVIEW. | | | | 1} THE RISER DIAGRAM INDICATES THE | | EQUIPMENT GROUND BEING RAN FROM THE | | METER TO THE DISCONNECT.PLEASE REMOVE | | SAME TO AVOID A PARALLEL GROUND/NEUTRAL | | PATH. | | | | 2} INCLUDE SMALL APPLIANCE CIRCUITS IN | | LOAD CALC. PER 220-30. | | | | 3} PLEASE LIST THE REQ'D ARC | | FAULT PROTECTED CIRCUITS ON PANEL | | SCHEDULE. PER 210-12 | | | | 4} LIST KITCHEN CIRCUITS ON PANEL | | SCHEDULE. | | | | 5} A/C #1 AHU @ 10K,BREAKER AND BRANCH | | CIRCUIT CONDUCTORS ARE UNDERSIZED. | | | | 6} THE WASHER IS LISTED AT 3000W IN THE | | LOAD CALCS AND SHOWN ON A 20 AMP BREAKER | | WITH #12 WIRE ON THE PANEL SCHEDULE, | | PLEASE CLARIFY. | | | | 7} OVEN SHOWN ON PANEL SCHEDULE, BUT NOT | | IN LOAD CALCS,PLEASE CLARIFY. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/659-8096 EXT. 8392 |
|