Plan Review Notes
Plan Review Notes For Permit 02041569
Permit Number 02041569
Review Stop M
Sequence Number 1
Notes
Date Text
2002-05-23 00:00:00PRIVISO
 #1 VARIFY TYPE OF VENTILATION USED FOR
 FRESH AIR NATURAL 402 OR
 MECHANICAL 403
 #2 CALCULATIONS FOR TYPE OF VENTILATION
 USED
 #3 REFER TO SECTION 604.1 BALANCED
 RETURN AIR
 #4 CONDENSATE DRAIN MUST TERMINATE
 12IN.FROM BUILDING
 PLAN REVIEW BY HAROLD MOSER
 [5612]659-8096 EXT.8390