Plan Review Notes For Permit 02041565 |
Permit Number |
02041565 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-05-23 00:00:00 | PROVISO | | #1 VARIFY TYPE OF VENTILATION FOR | | FRESH AIR USED NATURAL 402 OR | | MECHANICAL 403 | | #2 NEED CALCULATIONS FOR TYPE OF | | VENTILATION USED | | #3 REFER TO SECTION 601.4 BALANCED | | RETURN AIR | | #4 CONDENSATE DRAIN MUSE TERMINATE | | 12IN.FROM BUILDING | | PLAN REVIEW BY HAROLD MOSER | | [561]659-8096 EXT.8390 |
|