Plan Review Notes For Permit 02041552 |
Permit Number |
02041552 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-05-27 00:00:00 | PASSED/PROVISO | | | | 1) NEED REVISED PLAN BEFORE FINAL INSP- | | ECTION | | 2) VERIFY TYPE OF VENTILATION USED FOR | | FRESH AIR. NATURAL 402 OR MECHANICAL 403 | | 3) NEED CALCULATIONS FOR TYPE OF VENTIL- | | ATION USED. | | 4) REFER TO SECTION 403 MECHANICAL VENT- | | ILATION. NO WINDOW EXCEPTION. | | 5) CONDENSATE DRAIN MUST TERMINATE 12" | | FROM BLDG. 1503.4.4 | | | | PLAN REVIEW BY HAROLD MOSER | | (561) 659-8096 EXT 8390 | | PASSED/PRIVISO | | 1) NEED REVISER PLAN BEFORE FINAL | | INSPECTION | | 2) VERIFY TYPE OF VENTILATION USED FOR | | FRESH AIR.NATURAL 402 OR MECHANICAL | | 403 | | 3) NEED CALCULATIONS FOR TYPE OF | | VENTILATION USED | | 4) REFER TO SECTION 601.4 BALANCED | | RETURN AIR | | 5) REFER TO SECTION 403 MECHANICAL | | VENTILATION.NO WINDOW EXCEPTION | | 6) CONDENSATE DRAIN MUST TERMINATE 12" | | FROM BUILDING | | PLAN REVIEW BY HAROLD MOSER |
|