Plan Review Notes For Permit 02041473 |
Permit Number |
02041473 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-06-04 00:00:00 | *******************DENIED*************** | | | | MECHANICAL PERMIT 02041477 | | | | UNIT "B" - L | | 2001 FBC(M) 402.2 - NATURAL VENTILATION | | FOR OUTSIDE AIR REQUIRMENT. SHOW | | COMPLIANCE FOR THE MINIMUM OPENABLE AREA | | TO THE OUTDOORS. (4 PERCENT OF THE FLOOR | | AREA BEING VENTILATED) OR TABLE 403.3 | | FOR MECHANICAL VENTILATION. | | | | BALANCED RETURN AIR - 2001 FBC(M) 601.4 | | PRESSURE DIFFERNTIALS ACROSS CLOSED | | DOORS WHERE RETURNS ARE CENTRALLY | | LOCATED SHALL BE LIMITED TO .001" WC OR | | LESS. PROVIDE AIR DUCT PATHWAYS OR AIR | | TRANSFER PATHWAYS FROM THE HIGH PRESSURE | | ZONE TO THE LOW ZONE. | | | | CONDENSATE SHALL DISCHARGE A MINIMUM OF | | 12" AWAY FROM THE BUILDING STRUCTURE AS | | PER 2001 FBC 1503.4.4. | | | | REFERENCE DRYER LOCATION - SHALL HAVE | | PROTECTION FROM DAMAGE AS PER 2001 FBC, | | MECH 303.4. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|