Plan Review Notes
Plan Review Notes For Permit 02041461
Permit Number 02041461
Review Stop M
Sequence Number 1
Notes
Date Text
2002-06-04 00:00:00*******************DENIED***************
  
 MECHANICAL PERMIT 02041464
  
 UNIT "C" - L
 PLAN SHEET 14 SPLIT SYSTEM SCHEDULE
 INDICATES 10 SEER FOR THE C.U., ENERGY
 CALCS SHOW 11.0 SEER.
  
 BALANCED RETURN AIR - 2001 FBC(M) 601.4
 PRESSURE DIFFERNTIALS ACROSS CLOSED
 DOORS WHERE RETURNS ARE CENTRALLY
 LOCATED SHALL BE LIMITED TO .001" WC OR
 LESS. PROVIDE AIR DUCT PATHWAYS OR AIR
 TRANSFER PATHWAYS FROM THE HIGH PRESSURE
 ZONE TO THE LOW ZONE.
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.