| BUILDING PLAN REVIEW |
| PERMIT: 02041425 |
| ADD: 9717 BAYWINDS DR |
| CONT: SIERRA CONST |
| TEL: (305) 216-7981 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| THIRD REVIEW |
| |
| 1) PLANS SUBMITTED AFTER THE FEB 28/2002 |
| ARE TO BE DESIGNED TO THE 2001 FLORIDA |
| BUILDING CODE. |
| MANUFACTURED BUILDINGS- WHEN MANUFAC- |
| TURED BUILDINGS ARE BUILT UNDER THE 1997 |
| STANDARD BUILDING CODE AND THEY ARE THEN |
| MOVED FROM THE ORIGINAL PLACEMENT AND |
| PLANS ARE SUBMITTED, AFTER THE FEB 28, |
| 2002 DEADLINE, THEY ALSO MUST CONFORM TO |
| THE 2001 FLORIDA BUILDING CODE FOR WIND- |
| ZONES, (140 MPH, 3 SECOND GUST), IN PALM |
| BEACH COUNTY. |
| THIS STRUCTURE WOULD BE OK TO PLACE |
| IN A 110 MPH WIND ZONE. |
| THE ENGINEER OF RECORD FOR THE MANU- |
| FACTURED BUILDING COULD RECERTIFY THIS |
| BUILDING FOR 140 MPH, 3 SECOND GUST, |
| SHOW ENGINEERING FOR STRENGTHENING THE |
| STRUCTURE TO 140 MPH. |
| MANUFACTURED BUILDINGS- NEW CONSTRUC- |
| TION, APPROVAL DATE ON THE LISTING |
| AGENCY APPROVAL IS AFTER FEB 28,2002, |
| THIS NEW STRUCTURE MUST ALSO COMPLY WITH |
| THE WIND SPEED WHERE EVER THE UNIT IS TO |
| BE PLACED WITHIN THE STATE. |
| |
| 2)FL BLD CODE 2001 SECTION 103.6, |
| 1606.1.4, 1707.4 & 3401.7.2.4. |
| PROCEDURES: 1(B) A COMPLETE INSTALLATION |
| SCHEDULE SUMMARIZING & IDENTIFYING |
| OPENING SIZES, STORY HEIGHTS, UNIT MARK |
| NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM |
| BAR REINFORCING REQUIREMENTS, WALL PRES- |
| SURE ZONES, SLAT TYPES, ETC., SHALL BE |
| SUBMITTED AT TIME OF PERMIT APPLICATION |
| TO FACILITATE PLAN REVIEW AND PERMIT |
| ISSUANCE. |
| |
| BEFORE A PERMIT TO CONSTRUCT CAN BE |
| ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| BEACH CO.,THE PERMIT PLANS STAMPED BY |
| THEM AND THE RECEIPT ATTACHED TO THE |
| PERMIT APPLICATION. |