Plan Review Notes
Plan Review Notes For Permit 02041425
Permit Number 02041425
Review Stop B
Sequence Number 3
Notes
Date Text
2002-07-16 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02041425
 ADD: 9717 BAYWINDS DR
 CONT: SIERRA CONST
 TEL: (305) 216-7981
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 THIRD REVIEW
  
 1) PLANS SUBMITTED AFTER THE FEB 28/2002
 ARE TO BE DESIGNED TO THE 2001 FLORIDA
 BUILDING CODE.
 MANUFACTURED BUILDINGS- WHEN MANUFAC-
 TURED BUILDINGS ARE BUILT UNDER THE 1997
 STANDARD BUILDING CODE AND THEY ARE THEN
 MOVED FROM THE ORIGINAL PLACEMENT AND
 PLANS ARE SUBMITTED, AFTER THE FEB 28,
 2002 DEADLINE, THEY ALSO MUST CONFORM TO
 THE 2001 FLORIDA BUILDING CODE FOR WIND-
 ZONES, (140 MPH, 3 SECOND GUST), IN PALM
 BEACH COUNTY.
 THIS STRUCTURE WOULD BE OK TO PLACE
 IN A 110 MPH WIND ZONE.
 THE ENGINEER OF RECORD FOR THE MANU-
 FACTURED BUILDING COULD RECERTIFY THIS
 BUILDING FOR 140 MPH, 3 SECOND GUST,
 SHOW ENGINEERING FOR STRENGTHENING THE
 STRUCTURE TO 140 MPH.
 MANUFACTURED BUILDINGS- NEW CONSTRUC-
 TION, APPROVAL DATE ON THE LISTING
 AGENCY APPROVAL IS AFTER FEB 28,2002,
 THIS NEW STRUCTURE MUST ALSO COMPLY WITH
 THE WIND SPEED WHERE EVER THE UNIT IS TO
 BE PLACED WITHIN THE STATE.
  
 2)FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH CO.,THE PERMIT PLANS STAMPED BY
 THEM AND THE RECEIPT ATTACHED TO THE
 PERMIT APPLICATION.