Plan Review Notes
Plan Review Notes For Permit 02041425
Permit Number 02041425
Review Stop B
Sequence Number 2
Notes
Date Text
2002-06-24 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02041425
 ADD: 9717 BAYWINDS DRIVE
 CONT: SIERRA CONSTRUCTION
 TEL: (561)616-9686
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) PLANS SUBMITTED AFTER FEB. 28/ 2002
 ARE TO BE DESIGNED TO THE FL. BLD CODE.
 THE APPROVAL DATE FROM THE LISTING
 AGENCY APPROVAL IS 4/15/02. MISSING
 DCA LETTER.
 2)FIGURE 1606 WIND-BORNE DEBRIS
 REGION; INDICATES THAT W.P.B. CITY OF IS
 LOCATED IN THE 140 MPH ZONE. PLANS ARE
 TO INDICATE THIS.
 3)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
 4) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. ALL GLAZED OPENINGS
 REQUIRE PROTECTION, EITHER LARGE MISSLE
 IMPACT RESISTANCE PROTECTION OR STORM
 FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
 PLAN REVIEW
 JIM WITMER
 (561)659-8096X8412