Plan Review Notes For Permit 02041308 |
Permit Number |
02041308 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-05-04 00:00:00 | DENIED | | REFERENCE: FBC-2001 424.2 SWIMMING POOLS | | | | 1) PLEASE ADJUST YOUR NOTES, DETAILS, OR | | SUBMITTALS TO REFLECT THE FOLLOWING IN- | | FORMATION REQUIRED FOR PLAN REVIEW | | 2) | | FBC-2001 SEC 424.2.6.6.5 WHERE PROVIDED, | | THE VACUUM OR PRESSURE CLEANER FITTING | | SHALL BE LOCATED AT LEAST 6" AND NOT | | GREATER THAN 12" BELOW THE MINIMUM OPER- | | ATING WATER LEVEL OR AS AN ATTACHMENT TO | | THE SKIMMER. | | 3) | | FBC-2001 SEC 424.2.7.1 POOL CIRCULATING | | PUMPS SHALL BE EQUIPPED ON THE INLET | | SIDE WITH AN APPROVED TYPE HAIR AND LINT | | STRAINER WHEN USED WITH A PRESSURE FIL- | | TER. (DETAIL) | | 4) | | MAIN DRAIN DETAIL - SHOW 1'0" MAX TO | | VENT TIE-IN. | | 5) | | VENT DETAIL - LABEL VENT "POOL SAFETY | | DEVICE - DO NOT HANDLE" | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|