Plan Review Notes For Permit 02041275 |
Permit Number |
02041275 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-06-15 00:00:00 | DENIED | | REFERENCE: FBC-2001 CHAPTER 11 | | FBC-2001 PLUMBING | | | | 1) SHT M1 WATER HEATER DETAIL. DIELECT- | | RIC UNIONS NOT APPROVED FOR WATER PIPE. | | 2) SHT M1 WATER HEATER DETAIL. SHOWS | | DISCHARGE FROM P/T RELIEF VALVE TO FLOOR | | DRAIN. NOT APPROVED AS INDIRECT WASTE | | RECEPTOR. | | 3) SHT M1 WATER HEATER DETAIL. THERMAL | | EXPANSION CONTROL MAY BE REQUIRED IF A | | BACKFLOW IS INSTALLED ON WATER SERVICE. | | SEC 607.3 - 607.3.2 | | 4) SHT M1 NOTE #4, AIR CHAMBERS ARE NOT | | APPROVED. SEC 604.9 WATER HAMMER ARREST- | | ORS. | | 5) SHT A1.1 DRINKING FOUNTAIN. PLEASE | | PROVIDE DETAIL TO SHOW COMPLIANCE OF | | SECTION 4.15 AND ALL SUBSECTIONS. | | ALSO SEC 4.1.3(10) FOR THOSE WHO HAVE | | DIFFICULTY BENDING OR STOOPING. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|