2002-06-13 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) FBC 1606.1.4STOREFRONT ELEVATION
 A/A3 SHOWS THE REPLACEMENT OF EXISTING
 STOREFRONT FRAMING AND GLAZING.SUBMIT
 A PRODUCT APPROVAL FOR THE PROPOSED
 SYSTEM.
  
 3) FBC 11-4.16SHEET A3.1, EXISTING
 TOILET ROOM ELEVATIONS.ARE THE GRAB
 BARS AND OTHER FIXTURES EXISTING?
 IF NOT (REF. SHEET A8, SPECIFICATION
 ITEM 10), THEN THEY SHALL BE LOCATED AND
 INSTALLED TO COMPLY WITH THE
 REQUIREMENTS SHOWN IN FIG. 28, 29, 31
 AND 32.ANNOTATE AND DIMENSION THE
 PLANS TO DEMONSTRATE COMPLIANCE.THE
 GRAB RAIL BEHIND THE W.C. SHALL BE MIN.
 36" LONG.
  
 4) FBC 11-4.19SHEET A3.1ADD
 DIMENSIONS TO THE PLANS TO DEMONSTRATE
 COMPLIANCE WITH THE TOILET MIRROR
 MOUNTING HEIGHT REQUIREMENTS (FIG. 31).
  
 5) FBC 11-4.15 INTERIOR ELEVATION C/A3.1
 WORK ROOM DRINKING FOUNTAIN.ADD
 DIMENSIONS AND A SIDE ELEVATION OF THE
 DRINKING FOUNTAIN TO DEMONSTRATE
 COMPLIANCE WITH THE SPOUT HEIGHT AND LEG
 CLEARANCE REQUIREMENTS SHOWN IN FIG. 27
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499