2002-06-04 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 659 8096 EXT 8499 |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| |
| 1) FBC* 104.2.1.2THE SUBMITTED COPY OF |
| ROOF FRAMING PLAN A-05 HAS BEEN |
| REPRODUCED SUCH THAT THE UPLIFT MARKERS |
| AT THE LEFT EDGE HAVE BEEN TRUNCATED |
| AND ARE THEREFOR ILLEGIBLE.SUBMIT A |
| COMPLETE COPY. |
| |
| 2) FBC 1606.2.2.1THE DESIGN WIND |
| PRESSURES, ON THE ROOF FRAMING PLAN AND |
| GENERAL NOTES SHEET G1, HAVE BEEN |
| UNDERESTIMATED (REF FBC TABLE 1606.2B). |
| AMEND THE PRESSURES AND UPLIFTS AND |
| RESPECIFY THE TRUSS ANCHORS AS NECESSARY |
| TO DEMONSTRATE COMPLIANCE. |
| |
| 3) THE ATRIUM DOOR PRODUCT APPROVAL |
| NOTICE OF ACCEPTANCE NO. 01-0209.02 |
| EXPIRED PRIOR TO THE DATE OF APPLICATION |
| SUBMIT A CURRENT PRODUCT APPROVAL. |
| |
| 4) FIXED GLASS WINDOW PRODUCT APPROVAL |
| NOTICE OF ACCEPTANCE NO. 00-0512.02. |
| THE ASSOCIATED DRAWING SHEETS HAVE BEEN |
| UNNECESSARILY REDUCED DURING THE |
| COPYING PROCESS AND ARE NOT PROPERLY |
| LEGIBLE.SUBMIT LEGIBLE COPIES. |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |