Plan Review Notes
Plan Review Notes For Permit 02041267
Permit Number 02041267
Review Stop R
Sequence Number 1
Notes
Date Text
2002-06-04 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) FBC* 104.2.1.2THE SUBMITTED COPY OF
 ROOF FRAMING PLAN A-05 HAS BEEN
 REPRODUCED SUCH THAT THE UPLIFT MARKERS
 AT THE LEFT EDGE HAVE BEEN TRUNCATED
 AND ARE THEREFOR ILLEGIBLE.SUBMIT A
 COMPLETE COPY.
  
 2) FBC 1606.2.2.1THE DESIGN WIND
 PRESSURES, ON THE ROOF FRAMING PLAN AND
 GENERAL NOTES SHEET G1, HAVE BEEN
 UNDERESTIMATED (REF FBC TABLE 1606.2B).
 AMEND THE PRESSURES AND UPLIFTS AND
 RESPECIFY THE TRUSS ANCHORS AS NECESSARY
 TO DEMONSTRATE COMPLIANCE.
  
 3) THE ATRIUM DOOR PRODUCT APPROVAL
 NOTICE OF ACCEPTANCE NO. 01-0209.02
 EXPIRED PRIOR TO THE DATE OF APPLICATION
 SUBMIT A CURRENT PRODUCT APPROVAL.
  
 4) FIXED GLASS WINDOW PRODUCT APPROVAL
 NOTICE OF ACCEPTANCE NO. 00-0512.02.
 THE ASSOCIATED DRAWING SHEETS HAVE BEEN
 UNNECESSARILY REDUCED DURING THE
 COPYING PROCESS AND ARE NOT PROPERLY
 LEGIBLE.SUBMIT LEGIBLE COPIES.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499