2002-05-23 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE THAT ONLY ONE SET
 HAS A E-SHEET FOR MODEL "D". OTHER SET
 HAS TWO E MODEL SHEETS.
  
 2)NOTE: PLEASE NOTE POOL PANEL NOTES
 MOSTLY THE SAME A MODEL "B" COMMENTS.
 PLEASE NOTE ON THIS MODEL PUMP IS SHOWN
 AS 2P-30 AND PANEL IS SHOWN AS 2P-25
 ON MAIN PANEL SCHEDULE. PLEASE NOTE
 THIS NEEDS TO CORRELATE WITH RISER
 DIAGRAM. PLEASE ALSO NOTE THAT #6 AWG
 SHOWN WILL NOT FIT UNDER 2P30A OR 2P-25
  
 PLEASE SEE THE ABOVE NOTES AND SUBMIT
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  