Permit Number |
02041267 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-05-23 00:00:00 | **************** UNSAT ***************** | | | | 1)NOTE: PLEASE NOTE THAT ONLY ONE SET | | HAS A E-SHEET FOR MODEL "D". OTHER SET | | HAS TWO E MODEL SHEETS. | | | | 2)NOTE: PLEASE NOTE POOL PANEL NOTES | | MOSTLY THE SAME A MODEL "B" COMMENTS. | | PLEASE NOTE ON THIS MODEL PUMP IS SHOWN | | AS 2P-30 AND PANEL IS SHOWN AS 2P-25 | | ON MAIN PANEL SCHEDULE. PLEASE NOTE | | THIS NEEDS TO CORRELATE WITH RISER | | DIAGRAM. PLEASE ALSO NOTE THAT #6 AWG | | SHOWN WILL NOT FIT UNDER 2P30A OR 2P-25 | | | | PLEASE SEE THE ABOVE NOTES AND SUBMIT | | FOR REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|