2002-06-12 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 6/4/02:
  
 1) FBC 1606.1.1TRUSS DESIGN DOCUMENTS.
 THIS COMMENT HAS NOT BEEN ADDRESSED.
 THE TRUSS DESIGN CALCULATIONS, SHOP
 DRAWINGS AND LAYOUT DRAWING STILL REFER
 TO STANDARD BUILDING CODE 1997 AND A
 DESIGN WIND VELOCITY OF 110 MPH.THE
 FOOTNOTE ON EACH TRUSS SHEET STATES
 "TRUSS HAS BEEN CHECKED FOR 110 MPH WIND
 LOAD,....".AMEND THESE DOCUMENTS TO
 DEMONSTRATE COMPLIANCE WITH FLORIDA
 BUILDING CODE 2001.
  
 2) FBC 1606.2.2.1WIND PRESSURE.THE
 VELOCITY PRESSURE STATED ON GENERAL
 NOTES SHEET G1, AS 24.7PSF, DOES NOT
 CORRELATE TO THE CALCULATED VELOCITY
 PRESSURE OF 29.85PSF.AMEND SHEET G1.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499