Plan Review Notes
Plan Review Notes For Permit 02041257
Permit Number 02041257
Review Stop M
Sequence Number 2
Notes
Date Text
2002-06-18 00:00:00MODEL "B"
  
 2ND REQUEST
 MANUAL J CALCS NOT SUBMITTED - ENERGY
 CALCS INDICATE A 4 TON UNIT & PLAN
 SHOWS A 3.5 TON UNIT.
  
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.