Plan Review Notes For Permit 02041257 |
Permit Number |
02041257 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-05-23 00:00:00 | *************** UNSAT ************* | | | | 1)NOTE: PLEASE NOTE RISER DIAGRAM IS | | SHOWING A SEPARATE POOL PANEL DISC? | | PLEASE NOTE POOL PANEL IS SHOWN ON MAIN | | PANEL SCHEDULE ALONG WITH POOL PUMP | | COMING FROM MAIN PANEL ALSO? PLEASE | | NOTE POOL PANEL BEING SHOWN RIGHT NEXT | | TO MAIN PANEL. IF POOL PUMP IS COMING | | FROM MAIN PANEL, POOL PANEL IS FOR??? | | | | 2)NOTE: PLEASE NOTECONDUCTORS TO | | POOL PANEL NEED TO HAVE 2 HOTS,1-NEUTRAL | | AND AN EQUIPMENT GROUNDING CONDUCTOR | | WHICH IS NOT SHOWN??250-122 | | | | | | PLEASE MAKE THE CORRECTIONS. IF THERE | | ARE ANY CHANGES, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 | | | | | | *** PLEASE ALSO NOTE THAT THAT COVER | | SHEETS REF."LATEST EDITION OF NEC" | | PLEASE NOTE THIS NEEDS TO SHOW "99" | | THE "LATEST" EDITION WOULD MEAN 2002 NEC |
|