Plan Review Notes
Plan Review Notes For Permit 02041257
Permit Number 02041257
Review Stop E
Sequence Number 1
Notes
Date Text
2002-05-23 00:00:00*************** UNSAT *************
  
 1)NOTE: PLEASE NOTE RISER DIAGRAM IS
 SHOWING A SEPARATE POOL PANEL DISC?
 PLEASE NOTE POOL PANEL IS SHOWN ON MAIN
 PANEL SCHEDULE ALONG WITH POOL PUMP
 COMING FROM MAIN PANEL ALSO? PLEASE
 NOTE POOL PANEL BEING SHOWN RIGHT NEXT
 TO MAIN PANEL. IF POOL PUMP IS COMING
 FROM MAIN PANEL, POOL PANEL IS FOR???
  
 2)NOTE: PLEASE NOTECONDUCTORS TO
 POOL PANEL NEED TO HAVE 2 HOTS,1-NEUTRAL
 AND AN EQUIPMENT GROUNDING CONDUCTOR
 WHICH IS NOT SHOWN??250-122
  
  
 PLEASE MAKE THE CORRECTIONS. IF THERE
 ARE ANY CHANGES, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
  
  
 *** PLEASE ALSO NOTE THAT THAT COVER
 SHEETS REF."LATEST EDITION OF NEC"
 PLEASE NOTE THIS NEEDS TO SHOW "99"
 THE "LATEST" EDITION WOULD MEAN 2002 NEC