Plan Review Notes
Plan Review Notes For Permit 02041241
Permit Number 02041241
Review Stop R
Sequence Number 1
Notes
Date Text
2002-06-05 00:00:00BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, THE PERMIT PLANS STAMPED
 BY THAT OFFICE AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL 561-233-5025 FOR
 MORE INFORMATION.
  
 METRO DADE NOA 98-1110.06 IS EXPIRED.
  
 THE TRUSSES ARE DESIGNED TO THE 1997
 STANDARD BUILDING CODE, THEY ARE
 REQUIRED TO COMPLY WITH THE 2001 FBC.
 PLEASE REVISE AS NECESSARY.
  
 THE ENGINEER OF RECORD IS REQUIRED TO
 REVIEW THE DELEGATED DESIGN AREAS SUCH
 AS THE TRUSSES AND THE PRE-CAST WALL
 SYSTEM.PROVIDE DOCUMENTATION THAT THIS
 HAS BEEN DONE.
  
 THE ROYALL WALL PLANS DO NOT INDICATE
 THE SPECIFIC PROJECT OR CALCULATIONS.
 SEE RULE 61G15-31 OF THE FAC.
  
 THE ROYALL WALL PLANS DO NOT REFLECT
 THE DESIGN CRITERIA OF ACI 318-99 IN
 ACCORDANCE WITH FBC 1918.1 OR THE WIND
 DESIGN INFORMATION AS PROVIDED FOR IN
 FBC 1606.
  
 THE ENGINEER OF RECORD HAS NOT
 SPECIFIED ANY DESIGN CRITERIA FOR THE
 DELEGATED ENGINEERING DESIGN AS
 PROVIDED FOR IN 61G15-30.IN FACT, THE
 PLANS SHEETS ARE NOT EVEN NUMBERED.SEE
 ALSO, 61G15-30.003 RE: DOCUMENT
 CLASSIFICATION
  
 PROVIDE FOR TERMITE PROTECTION IN
 ACCORDANCE WITH FBC 1816.1.7.
  
 SHOW THE INTERNAL PRESSURE COEFFICIENT
 AND COMPONENT & CLADDING PRESSURES FOR
 THE ROOF COVERING.SEE FBC 1606.1.7.