2002-06-05 00:00:00 | BEFORE A PERMIT TO CONSTRUCT MAY BE |
| ISSUED IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, THE PERMIT PLANS STAMPED |
| BY THAT OFFICE AND A COPY OF THE PAID |
| RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION.CALL 561-233-5025 FOR |
| MORE INFORMATION. |
| |
| METRO DADE NOA 98-1110.06 IS EXPIRED. |
| |
| THE TRUSSES ARE DESIGNED TO THE 1997 |
| STANDARD BUILDING CODE, THEY ARE |
| REQUIRED TO COMPLY WITH THE 2001 FBC. |
| PLEASE REVISE AS NECESSARY. |
| |
| THE ENGINEER OF RECORD IS REQUIRED TO |
| REVIEW THE DELEGATED DESIGN AREAS SUCH |
| AS THE TRUSSES AND THE PRE-CAST WALL |
| SYSTEM.PROVIDE DOCUMENTATION THAT THIS |
| HAS BEEN DONE. |
| |
| THE ROYALL WALL PLANS DO NOT INDICATE |
| THE SPECIFIC PROJECT OR CALCULATIONS. |
| SEE RULE 61G15-31 OF THE FAC. |
| |
| THE ROYALL WALL PLANS DO NOT REFLECT |
| THE DESIGN CRITERIA OF ACI 318-99 IN |
| ACCORDANCE WITH FBC 1918.1 OR THE WIND |
| DESIGN INFORMATION AS PROVIDED FOR IN |
| FBC 1606. |
| |
| THE ENGINEER OF RECORD HAS NOT |
| SPECIFIED ANY DESIGN CRITERIA FOR THE |
| DELEGATED ENGINEERING DESIGN AS |
| PROVIDED FOR IN 61G15-30.IN FACT, THE |
| PLANS SHEETS ARE NOT EVEN NUMBERED.SEE |
| ALSO, 61G15-30.003 RE: DOCUMENT |
| CLASSIFICATION |
| |
| PROVIDE FOR TERMITE PROTECTION IN |
| ACCORDANCE WITH FBC 1816.1.7. |
| |
| SHOW THE INTERNAL PRESSURE COEFFICIENT |
| AND COMPONENT & CLADDING PRESSURES FOR |
| THE ROOF COVERING.SEE FBC 1606.1.7. |