Plan Review Notes For Permit 02041241 |
Permit Number |
02041241 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-05-01 00:00:00 | ~~~~~~~~~~~~~~~~~UNSAT!~~~~~~~~~~~~~~~~~ | | | | PLEASE PROVIDE THE FOLLOWING | | INFORMATIONAND MAKE ANY NECESSARY | | CHANGES TO THE PLANS AND RESUBMIT FOR | | REVIEW: | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 2} PLEASE NOTE MISSING DISCONNECT | | FOR A/C CONDENSOR,MUST CONFORM TO | | 440-14NEC. | | | | 3}PLEASE NOTE THAT ALL PLANS | | THAT ARE SIGNED AND SEALED BY ARCH/ OR | | ENGINEER ARE REQ`D PER 61G15-23.002 FOR | | ENGINEER AND 61G1-16.004 FOR ARCH.(TITLE | | BLOCK). | | | | 4}PLEASE LIST THE REQ`D ARC | | FAULT PROECTED CIRCUITS ON PANEL | | SCHEDULE. PER 210-12 | | | | | | 5} RECEPTACLE SPACING TO COMPLY WITH ART | | ICLE 210-52(A). | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/659-8096 |
|