2002-05-01 00:00:00~~~~~~~~~~~~~~~~~UNSAT!~~~~~~~~~~~~~~~~~
  
 PLEASE PROVIDE THE FOLLOWING
 INFORMATIONAND MAKE ANY NECESSARY
 CHANGES TO THE PLANS AND RESUBMIT FOR
 REVIEW:
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
  
 2} PLEASE NOTE MISSING DISCONNECT
 FOR A/C CONDENSOR,MUST CONFORM TO
 440-14NEC.
  
 3}PLEASE NOTE THAT ALL PLANS
 THAT ARE SIGNED AND SEALED BY ARCH/ OR
 ENGINEER ARE REQ`D PER 61G15-23.002 FOR
 ENGINEER AND 61G1-16.004 FOR ARCH.(TITLE
 BLOCK).
  
 4}PLEASE LIST THE REQ`D ARC
 FAULT PROECTED CIRCUITS ON PANEL
 SCHEDULE. PER 210-12
  
  
 5} RECEPTACLE SPACING TO COMPLY WITH ART
 ICLE 210-52(A).
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096