Plan Review Notes
Plan Review Notes For Permit 02041152
Permit Number 02041152
Review Stop P
Sequence Number 1
Notes
Date Text
2002-05-11 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BLDG CHAPTER 11
  
 1) SHTS A-1 & P-2.1 DOOR SHALL NOT OPEN
 INTO CLEAR FLOOR SPACE OF AND ACCESSIBLE
 FIXTURE.
 2) FBC PLMG TABLE REQUIRES A DRINKING
 FOUNTAIN & AND A SERVICE SINK. PLEASE
 PROVIDE REQUIRED FIXTURES.
 3) SHT P0.1 PLUMBING NOTES #23, CONDEN-
 SATE LINES AS SHOWN ON SHT P2.1 FBC SEC
 1503.4.4 REQUIRES THAT DISCHARGE FROM
 CONDENSATE BE MINIMUM OF 12" FROM BLDG.
 4) SHT PO.1 PLUMBING NOTES #13 AIR CHAM-
 BERS NOT APPROVED, DELETE REFERENCE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377