1 |
|
Notes |
Date |
Text |
2002-05-11 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 BLDG CHAPTER 11 | | | | 1) SHTS A-1 & P-2.1 DOOR SHALL NOT OPEN | | INTO CLEAR FLOOR SPACE OF AND ACCESSIBLE | | FIXTURE. | | 2) FBC PLMG TABLE REQUIRES A DRINKING | | FOUNTAIN & AND A SERVICE SINK. PLEASE | | PROVIDE REQUIRED FIXTURES. | | 3) SHT P0.1 PLUMBING NOTES #23, CONDEN- | | SATE LINES AS SHOWN ON SHT P2.1 FBC SEC | | 1503.4.4 REQUIRES THAT DISCHARGE FROM | | CONDENSATE BE MINIMUM OF 12" FROM BLDG. | | 4) SHT PO.1 PLUMBING NOTES #13 AIR CHAM- | | BERS NOT APPROVED, DELETE REFERENCE. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|