Plan Review Notes For Permit 02041062 |
Permit Number |
02041062 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-05-18 00:00:00 | PRIVISO | | #1 VARIFY TYPE OF VENTILATION USED | | [FRESH AIR]NATURAL 402 OR | | MECHANICAL 403 | | #2 NEED CALCULATIONS FOR TYPE OF | | VANTILATION USED | | #3 REFER TO SECTION 601.4 BALANCED | | RETURN AIR | | #4 CONDENSATE DRAIN MUST TERMINATE | | 12IN.FROM BUILDING 1503.4.4 | | #5 NEED MANUFACTURER'S INSTRUCTIONS | | ON COOKTOP | | #6 NEED RETURN AIR SIZES | | #7 MEED PRESSURE TEST ON REFRIGERANT | | LINES SECTION 1108 | | #8 ALL REFRIGERANT PIPING UNDER SLAB | | SHALL BE INCASED IN PIPE DUCT 1107.2. | | CALL FOR INSPECTIONPRIER TO COVERING | | PIPE SLEEVE WITH DIRT | | PLAN REVIEW BY HAROLD MOSER | | [561]659-8096 EXT 8390 |
|