Plan Review Notes For Permit 02041062 |
Permit Number |
02041062 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-05-21 00:00:00 | UNSAT! | | ~~~~~~ | | | | PLLEASE PROVIDE THE FOLLOWING | | INFORMATION,MAKE ANY NECESSARY CHANGES | | TO PLANS AND RESUBMIT FOR REVIEW: | | | | 1} PLEASE NOTE THAT THERE IS AN | | ENGINEERS SEAL WITHOUT A TITLE BLOCK ON | | SHEETS S-1 THROUGH S-6,FS/FAC 471-025. | | | | 2} INDICATE FEEDER CONDUCTOR SIZE TO | | "P"PANEL,AND CONDUIT TYPE AND SIZE.(IS | | A TAP RULE BEING USED FOR THIS FEEDER | | AND IF SO INDICATE WHICH ONE). | | | | 3} NOTE THE PHASES ON THE PANEL SCHEDULE | | ARE MARKED "A" & "C" INSTEAD OF "A"&"B" | | | | 4} PANEL "P" AMPS PER PHASE ARE LARGER | | THAN THE OCP. | | | | 5} PANEL "B" AMPS PER PHASE APPEAR TO BE | | INCORRECT. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | 561/659-8096 EXT. 8392 |
|