Plan Review Notes
Plan Review Notes For Permit 02041062
Permit Number 02041062
Review Stop E
Sequence Number 1
Notes
Date Text
2002-05-21 00:00:00UNSAT!
 ~~~~~~
  
 PLLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE ANY NECESSARY CHANGES
 TO PLANS AND RESUBMIT FOR REVIEW:
  
 1} PLEASE NOTE THAT THERE IS AN
 ENGINEERS SEAL WITHOUT A TITLE BLOCK ON
 SHEETS S-1 THROUGH S-6,FS/FAC 471-025.
  
 2} INDICATE FEEDER CONDUCTOR SIZE TO
 "P"PANEL,AND CONDUIT TYPE AND SIZE.(IS
 A TAP RULE BEING USED FOR THIS FEEDER
 AND IF SO INDICATE WHICH ONE).
  
 3} NOTE THE PHASES ON THE PANEL SCHEDULE
 ARE MARKED "A" & "C" INSTEAD OF "A"&"B"
  
 4} PANEL "P" AMPS PER PHASE ARE LARGER
 THAN THE OCP.
  
 5} PANEL "B" AMPS PER PHASE APPEAR TO BE
 INCORRECT.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT. 8392