Plan Review Notes For Permit 02041028
Permit Number 02041028
Review Stop E
Sequence Number 1
Notes
Date Text
2002-05-06 00:00:00~~~~~~~~~~~~~~~~~UNSAT!~~~~~~~~~~~~~~~~~
  
 1} PLEASE UPDATE THE ELECTRICAL NOTES ON
 SHEET E-2 TO REFLECT THE CURRENT
 (1999)NEC.
  
 2} PROVIDE RECEPTACLE AT A/C CONDENSORS
 PER 210-63.
  
 3} ADD A SMOKE DETECTOR IN THE DEN PER
 2-2.1.1.1 NFPA-72.
  
 4} ADD A SMOKE DETECTOR IN THE HALLWAY
 TO SERVE THE MASTER BEDROOM AND BEDROOM
 #2.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT.8392