Plan Review Notes For Permit 02041028 |
Permit Number |
02041028 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-05-06 00:00:00 | ~~~~~~~~~~~~~~~~~UNSAT!~~~~~~~~~~~~~~~~~ | | | | 1} PLEASE UPDATE THE ELECTRICAL NOTES ON | | SHEET E-2 TO REFLECT THE CURRENT | | (1999)NEC. | | | | 2} PROVIDE RECEPTACLE AT A/C CONDENSORS | | PER 210-63. | | | | 3} ADD A SMOKE DETECTOR IN THE DEN PER | | 2-2.1.1.1 NFPA-72. | | | | 4} ADD A SMOKE DETECTOR IN THE HALLWAY | | TO SERVE THE MASTER BEDROOM AND BEDROOM | | #2. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/659-8096 EXT.8392 |
|