Date Text
2002-04-27 00:00:00DENIED;
 1.PLUMBING RISER DIAGRAM. MASTER BATH
 NO MORE THAN 4 FIXTURE UNITS PERMITED
 ON A 2" WET VENT. SIZE OF PIPE TO BE
 3" AFTER TUB. TABLE 909.3.
 NOTES;
 NOTE #3 MINIMUM SLOPE OF PIPE TO COMPLY
 WITH TABLE 704.1. PIPE LESS THAN
 3" SHALL SLOPE AT 1/4".
 NOTE#5 NO FLOOR DRAINS SHOWN ON DRAWING.
 NOTE NOT NEEDED.
 NOTE#6 CONDENSATE IS NOT PERMITED TO
 DUMP INTO SANITARY SEWER SYSTEM
 CITY UTILITY'S REQUIREMENT.
 NOTE#7 WATER HAMMER ARRESTORS ARE
 REQUIRED. SEE SEC. 604.9 FOR
 LOCATIONS REQUIRED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8369