2002-04-27 00:00:00 | DENIED; | | 1.PLUMBING RISER DIAGRAM. MASTER BATH | | NO MORE THAN 4 FIXTURE UNITS PERMITED | | ON A 2" WET VENT. SIZE OF PIPE TO BE | | 3" AFTER TUB. TABLE 909.3. | | NOTES; | | NOTE #3 MINIMUM SLOPE OF PIPE TO COMPLY | | WITH TABLE 704.1. PIPE LESS THAN | | 3" SHALL SLOPE AT 1/4". | | NOTE#5 NO FLOOR DRAINS SHOWN ON DRAWING. | | NOTE NOT NEEDED. | | NOTE#6 CONDENSATE IS NOT PERMITED TO | | DUMP INTO SANITARY SEWER SYSTEM | | CITY UTILITY'S REQUIREMENT. | | NOTE#7 WATER HAMMER ARRESTORS ARE | | REQUIRED. SEE SEC. 604.9 FOR | | LOCATIONS REQUIRED. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 659-8096 EXT. 8369 |
|