2002-05-08 00:00:00 | ***************** UNSAT ************* |
| |
| 1) NOTE: SMOKE DETECTORS ARE REQUIRED |
| INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| DWELLING UNIT. ROOMS WITH BATHS AND OR |
| CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| PER NFPA-72 2-2.1.1.1. |
| IN THE VICINITY OF BEDROOMS AND CLOSE |
| PROXIMITY OF STIRWAYS. 2-5.2.1.3 |
| 3'FT FROM BATHS/KITCHENS.2-5.2.1.6 |
| PLEASE NOTE MISSING FROM DOWNSTAIRS |
| BEDROOM. |
| |
| 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW EQUIPMENT BEING INSTALLED. |
| MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| THE AVAILABLE FAULT CURRENT PER 110-9. |
| |
| 3) NOTE: PLEASE SHOW ALL OUTLET SPACING |
| TO MEET 2`,6`,12` RULE PER 210-52. |
| MISSING UPSTAIRS BED RM. |
| |
| 4)NOTE: PLEASE NOTE MISSING OUTLET FOR |
| A/C EQUIPMENT. PER 210-63 AND/OR SECTION |
| 306 OF THE MECHANICAL CODE. |
| |
| 6) NOTE: PLEASE SHOW GROUNDING ELECTRODE |
| GOING TO BUILDING STEEL AND COLD WATER |
| PER 250-50. SIZE PER 250-66 |
| |
| 7))NOTE: PLEASE CLARIFY EQUIPMENT |
| GROUNDING METHOD BETWEEN FIRST MEANS |
| OF DISCONNECT AND PANELS. PLEASE SIZE |
| CONDUCTORS PER 250-122. |
| |
| 8)NOTE: PLEASE NOTE THAT PER LOCAL |
| AMENDMENTS ALL SERVICE ENTRANCE CONDUCT- |
| ORS SHALL BE IN A RACEWAY SPECIFIED IN |
| 230-43. |
| PLEASE ALSO NOTE THAT NO ALUM CONDUCTORS |
| MAY BE USED SMALLER THAN #2. 310-2 |
| AND NO ALUM FOR GROUNDING/OR BONDING. |
| 310-2B 1&2 |
| |
| 9)NOTE: PLEASE NOTE MISSING A/C DISC`S |
| FOR AHU`S PER 440-11 |
| |
| |
| |
| |
| |
| |
| 11)NOTE: PLEASE NOTE,ELECTRICAL NOTE |
| ON PLANS MENTIONS TO PLACE SD`S ON BATH |
| AND KITCHEN CIRCUIT? PLEASE CLARIFY |
| LIGHTING CIRCUIT??? 210-11-C1/210-11C-3 |
| |
| 12)NOTE: PLEASE LIST THE REQ`D ARC FAULT |
| PROTECTED CIRCUITS PER 210-12 |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-659-8096 EXT 8372 |