2002-05-08 00:00:00******************* UNSAT *************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2) NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL AND COLD WATER
 PER 250-50. SIZE PER 250-66
  
 3)NOTE: PLEASE NOTE MISSING OUTLET FOR
 A/C EQUIPMENT. PER 210-63 AND/OR SECTION
 306 OF THE MECHANICAL CODE.
  
 4))NOTE: PLEASE CLARIFY EQUIPMENT
 GROUNDING METHOD BETWEEN FIRST MEANS
 OF DISCONNECT AND PANELS. PLEASE SIZE
 CONDUCTORS PER 250-122.
  
 5) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
 210-52H HALLWAY MASTER BR.
  
 6)) NOTE: PLEASE NOTE FRONT AND REAR
 RECEPTS REQ`D PER 210-52E
 MISSING REAR.
  
 7 )NOTE: PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE. PER 210-12
  
 8)NOTE: PLEASE NOTE THAT PER LOCAL
 AMENDMENTS, ALL SERVICE ENTRANCE
 CONDUCTORS AND FEEDER TO PANELS SHALL
 BE IN A RACEWAY.230-43 OF THE LOCAL
 CODE. PLEASE NOTE NO ALUM CONDUCTORS OF
 ANY KIND SMALLER THAN #2 IS PERMITTED.
 PLEASE ASLO NOTE THAT NO ALUM CONDUCTORS
 CAN BE USED FOR GROUNDING OR BONDING.
 310-2
  
 9)NOTE: PLEASE NOTE THAT ELECTRRICAL
 NOTES MENTION, SD`S TO COME FROM BATH
 AND KITCHEN CIRCUITS? PLEASE CLARIFY?
 LIGHTING? PLEASE NOTE 210-11-C1/C1
  
 PLEASE SUBMIT THE ABOVE INFORMAITON FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  