2002-05-08 00:00:00 | ******************* UNSAT ************* |
| |
| 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW EQUIPMENT BEING INSTALLED. |
| MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| THE AVAILABLE FAULT CURRENT PER 110-9. |
| |
| 2) NOTE: PLEASE SHOW GROUNDING ELECTRODE |
| GOING TO BUILDING STEEL AND COLD WATER |
| PER 250-50. SIZE PER 250-66 |
| |
| 3)NOTE: PLEASE NOTE MISSING OUTLET FOR |
| A/C EQUIPMENT. PER 210-63 AND/OR SECTION |
| 306 OF THE MECHANICAL CODE. |
| |
| 4))NOTE: PLEASE CLARIFY EQUIPMENT |
| GROUNDING METHOD BETWEEN FIRST MEANS |
| OF DISCONNECT AND PANELS. PLEASE SIZE |
| CONDUCTORS PER 250-122. |
| |
| 5) NOTE: PLEASE SHOW ALL OUTLET SPACING |
| TO MEET 2`,6`,12` RULE PER 210-52. |
| 210-52H HALLWAY MASTER BR. |
| |
| 6)) NOTE: PLEASE NOTE FRONT AND REAR |
| RECEPTS REQ`D PER 210-52E |
| MISSING REAR. |
| |
| 7 )NOTE: PLEASE LIST THE REQ`D ARC |
| FAULT PROTECTED CIRCUITS ON PANEL |
| SCHEDULE. PER 210-12 |
| |
| 8)NOTE: PLEASE NOTE THAT PER LOCAL |
| AMENDMENTS, ALL SERVICE ENTRANCE |
| CONDUCTORS AND FEEDER TO PANELS SHALL |
| BE IN A RACEWAY.230-43 OF THE LOCAL |
| CODE. PLEASE NOTE NO ALUM CONDUCTORS OF |
| ANY KIND SMALLER THAN #2 IS PERMITTED. |
| PLEASE ASLO NOTE THAT NO ALUM CONDUCTORS |
| CAN BE USED FOR GROUNDING OR BONDING. |
| 310-2 |
| |
| 9)NOTE: PLEASE NOTE THAT ELECTRRICAL |
| NOTES MENTION, SD`S TO COME FROM BATH |
| AND KITCHEN CIRCUITS? PLEASE CLARIFY? |
| LIGHTING? PLEASE NOTE 210-11-C1/C1 |
| |
| PLEASE SUBMIT THE ABOVE INFORMAITON FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-659-8096 EXT 8372 |