2002-05-08 00:00:00 | ****************** UNSAT ************* |
| |
| 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW EQUIPMENT BEING INSTALLED. |
| MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| THE AVAILABLE FAULT CURRENT PER 110-9. |
| |
| 2) NOTE: PLEASE SHOW GROUNDING ELECTRODE |
| GOING TO BUILDING STEEL AND COLD WATER |
| PER 250-50. SIZE PER 250-66 |
| |
| 3) NOTE: PLEASE SHOW ALL OUTLET SPACING |
| TO MEET 2`,6`,12` RULE PER 210-52. |
| MISSING BED RM |
| |
| 4)NOTE: PLEASE NOTE MISSING OUTLET FOR |
| A/C EQUIPMENT. PER 210-63 AND/OR SECTION |
| 306 OF THE MECHANICAL CODE. |
| |
| 5))NOTE: PLEASE LIST THE REQ`D ARC |
| FAULT PROTECTED CIRCUITS ON PANEL |
| SCHEDULE. PER 210-12 |
| |
| 6)NOTE: PLEASE NOTE THAT PER LOCAL |
| AMENDMENTS , ALL SERVICE ENTRANCE |
| CONDUCTORS SHALL BE IN A RACEWAY AS |
| SPECIFIED IN 230-43 OF THE LOCAL CODE. |
| PLEASE ALSO NOTE NO ALUM CONDUCTORS OF |
| ANY KIND SMALLER THAN #2 AND NONE FOR |
| GROUNDING OR BONDING. 310-2 |
| |
| 7)NOTE: PLEASE NOTE THAT ELECTRICAL |
| NOTES MENTIONS TO PLACE SD`S ON KITCHEN |
| AND BATH CIRCUITS? PLEASE CLARIFY. |
| LIGHTING? |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |