Plan Review Notes
Plan Review Notes For Permit 02040977
Permit Number 02040977
Review Stop E
Sequence Number 1
Notes
Date Text
2002-05-08 00:00:00****************** UNSAT *************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2) NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL AND COLD WATER
 PER 250-50. SIZE PER 250-66
  
 3) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
 MISSING BED RM
  
 4)NOTE: PLEASE NOTE MISSING OUTLET FOR
 A/C EQUIPMENT. PER 210-63 AND/OR SECTION
 306 OF THE MECHANICAL CODE.
  
 5))NOTE: PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE. PER 210-12
  
 6)NOTE: PLEASE NOTE THAT PER LOCAL
 AMENDMENTS , ALL SERVICE ENTRANCE
 CONDUCTORS SHALL BE IN A RACEWAY AS
 SPECIFIED IN 230-43 OF THE LOCAL CODE.
 PLEASE ALSO NOTE NO ALUM CONDUCTORS OF
 ANY KIND SMALLER THAN #2 AND NONE FOR
 GROUNDING OR BONDING. 310-2
  
 7)NOTE: PLEASE NOTE THAT ELECTRICAL
 NOTES MENTIONS TO PLACE SD`S ON KITCHEN
 AND BATH CIRCUITS? PLEASE CLARIFY.
 LIGHTING?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372