Plan Review Notes
Plan Review Notes For Permit 02040974
Permit Number 02040974
Review Stop E
Sequence Number 1
Notes
Date Text
2002-05-08 00:00:00************ UNSAT ******************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2) NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL AND COLD WATER
 PER 250-50. SIZE PER 250-66
  
 3)NOTE: PLEASE NOTE MISSING OUTLET FOR
 A/C EQUIPMENT. PER 210-63 AND/OR SECTION
 306 OF THE MECHANICAL CODE.
  
 4))NOTE: PLEASE CLARIFY EQUIPMENT
 GROUNDING METHOD BETWEEN FIRST MEANS
 OF DISCONNECT AND PANELS. PLEASE SIZE
 CONDUCTORS PER 250-122.
  
 5))NOTE: PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE. PER 210-12
  
 6)NOTE: PLEASE NOTE THAT PER LOCAL
 AMENDMENTS, ALL SERVICE ENTRANCE
 CONDUCTORS SHALL BE IN A RACEWAY AS
 SPECIFIED IN 230-43 OF THE LOCAL CODE.
 PLEASE ALSO NOTE NO ALUM CONDUCTORS
 OF ANY KIND SMALLER THAN #2 AND NONE
 USED FOR GROUNDING OR BONDING. 310-2
  
 7)NOTE: PLEASE NOTE THAT ELECTRICAL
 NOTES MENTIONS TO PLACE SD`S ON BATH
 AND KITCHEN CIRCUITS? PLEASE CLARIFY,,
 LIGHTING?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
  
  
 8)NOTE: PLEASE NOTE MISSING HALLWAY REC
 MASTER BR. 210-52H