Plan Review Notes
Plan Review Notes For Permit 02040884
Permit Number 02040884
Review Stop E
Sequence Number 1
Notes
Date Text
2002-04-22 00:00:00******************UNSAT!****************
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 AND RESUBMIT FOR REVIEW:
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} PLEASE NOTE KITCHEN COUNTER-
 -SPACE RECEPT SPACING SHALL MEET ART;
 210-52C 1,2,3,4,AND 5.
  
 3} PLEASE NOTE THE WORKING CLEARANCE
 FOR THE WATER HEATER AND PANEL MUST
 COMPLY WITH ARTICLE 110-26.
  
 4} INDICATE THE SIZE OF THE SERVICE
 ENTRANCE CONDUCTORS IN THE RISER.
  
 5} INDICATE HOW THE PANEL IS BEING FED
 FROM THE DISCONNECT(CONDUIT
 WIRE,GROUND- ING CONDUTOR SIZE,ETC.)
  
 6} DRYER CIRCUIT TO COMPLY WITH 250-138.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT.8392