Plan Review Notes For Permit 02040884 |
Permit Number |
02040884 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-04-22 00:00:00 | ******************UNSAT!**************** | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | AND RESUBMIT FOR REVIEW: | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | 2} PLEASE NOTE KITCHEN COUNTER- | | -SPACE RECEPT SPACING SHALL MEET ART; | | 210-52C 1,2,3,4,AND 5. | | | | 3} PLEASE NOTE THE WORKING CLEARANCE | | FOR THE WATER HEATER AND PANEL MUST | | COMPLY WITH ARTICLE 110-26. | | | | 4} INDICATE THE SIZE OF THE SERVICE | | ENTRANCE CONDUCTORS IN THE RISER. | | | | 5} INDICATE HOW THE PANEL IS BEING FED | | FROM THE DISCONNECT(CONDUIT | | WIRE,GROUND- ING CONDUTOR SIZE,ETC.) | | | | 6} DRYER CIRCUIT TO COMPLY WITH 250-138. | | | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | 561/659-8096 EXT.8392 |
|