Plan Review Notes For Permit 02040826 |
Permit Number |
02040826 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2002-05-07 00:00:00 | ****************** UNSAT *************** | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | 2 )NOTE: PLEASE LIST THE REQ`D ARC | | FAULT PROTECTEDCIRCUITS ON PANEL | | SCHEDULE. PER 210-12 | | | | 3)NOTE: PLEASE NOTE LOAD OF 5KW FOR | | DRYER ON #12. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|