Plan Review Notes
Plan Review Notes For Permit 02040817
Permit Number 02040817
Review Stop E
Sequence Number 2
Notes
Date Text
2002-05-07 00:00:00******************** UNSAT ************
  
 1 NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2)NOTE: PLEASE NOTE MISSING REQ`D
 LISTING ON PANEL SCHEDULE FOR ARC FAULT
 PROTECTION PER 210-12.
  
 3)NOTE: PLEASE NOTE #12 SHOWN FOR DRYER
 AT 5KW. #10?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  