Plan Review Notes
Plan Review Notes For Permit 02040747
Permit Number 02040747
Review Stop E
Sequence Number 2
Notes
Date Text
2002-05-07 00:00:00************ UNSAT ************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2))NOTE: PLEASE LIST THE REQ`D ARC
 FAULT PROTECTEDCIRCUITS ON PANEL
 SCHEDULE. PER 210-12
  
 3)NOTE: PLEASE NOTE 5KW LOAD FOR DRYER
 ON #12 AWG.
  
 PLEASE SUBMIT THAT ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372