Plan Review Notes
Plan Review Notes For Permit 02040708
Permit Number 02040708
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-05-02 00:00:00A) A MINIMUM OF A 2" PIPE IS TO BE
 PROVIDED FOR VENTING. THIS PIPE IS TO
 BE AT LEAST 12 FEET HIGH.
 B) APPROPRIATE LABELS, WARNING SIGNS,
 ARE TO BE PROVIDED FOR THE TANK.
 C) THE TWO HOUR AREA IS TO BE FIRE
 SPRINKLER PROTECTED.
 D) SEPARATE PLANS ARE REQUIRED FOR
 PIPING FROM THE FUEL TANK TO THE
 GENERATOR.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910