Plan Review Notes For Permit 02040691 |
Permit Number |
02040691 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-05-07 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | | | 1) SHT #1 PLEASE GIVE DIMENSIONS FOR | | EXISTING RESTROOMS. | | 2) SHT #1 DOOR SWING SHALL NOT OPEN INTO | | THE CLEAR FLOOR SPACE OF HDCP LAV. FBC- | | 2001 SEC 4.17.3 | | 3) SHT #1 SI SINK SHALL COMPLY WITH SEC | | 11-424. GIVE DETAILS FOR ALL SUBSECTIONS | | 4) SHTS #1 & #3 JANITOR SINK REFERED TO | | ON SANT. RISER DIAGRAM NOT SHOWN ON DEMO | | SHT OR FLOOR PLAN?? PLEASE SHOW JANITOR | | SINK OF FLOOR PLAN. (TABLE 403.1 - FBC- | | 2001 PLUMBING REQUIRES 1 SERVICE SINK). | | 5) SHT #3 PLUMBING NOTE #7 - AIR CHAMB- | | ERS ARE NOT APPROVED. WATER HAMMER ARRES | | TORS ARE REQUIRED ON ALL QUICK CLOSING | | VALVES ONLY. (WASH MACHINES, ICE MAKERS, | | DISHWASHERS ECT.) IF USED THEY SHALL BE | | LOCATED NEAR FIXTURE, IN AN "EFFECTIVE | | RANGE", NOT AT TOP OF DROP. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|