2002-05-03 00:00:00 | PROVISO: | | | | CONDENSER UNIT STANDS SHALL COMPLY WITH | | 2001 FBC TABLE 1511.7. | | | | EQUIPMENT INSTALLED ON ROOFS THAT EXCEED | | 16 FT IN HEIGHT SHALL HAVE AN APPROVED | | PERMANENT MEANS OF ACCESS.SUCH ACCESS | | SHALL NOT REQUIRED CLIMBING OVER | | OBSTRUCTIONS GREATER THAN 30 IN.2001 | | FBC(M) 306.5 | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|