Plan Review Notes
Plan Review Notes For Permit 02040691
Permit Number 02040691
Review Stop B
Sequence Number 1
Notes
Date Text
2002-04-23 00:00:00BUILDING PLAN REVIEW
 PERMIT # 02040691
 423 4TH ST
 SISCA CONSTRUCTION
 TEL: 686-9538
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1)- EXISTING RATED STAIRWAY LEADING
 THROUGH THE EXISTING VESYIBLE, AS INDICA
 TED ON THE FLOOR PLAN THIS IS THE ONLY
 AREA THAT REQUIRES A 1 HR FIRE RATING,
 FL BLD CODE 704.2.4 REQUIRES CORRIDORS
 EXIT ENCLOSURES AND FIRE RATED WALLS
 REQUIRED TO HAVE PROTECTED OPENINGS
 SHALL BE EFFECTIVELY AND PERMANENTLY
 WITH SIGN OR STENCILING, FIRE WALL &
 SMOKE BARRIER PROTECT ALL OPENINGS.
  
 2)- FL BLD CODE 104.2.1.2 ADDITIONAL
 DATA REQUIRED, THE HANDICAPPED RESTROOMS
 ARE NOT DIMENSIONED, PLEASE PROVIDE THIS
 ADDTIONAL INFORMATION. THE MINIMUM DIS-
 TANCE BETWEEN FIXTURES SHALL BE GIVEN BY
 THE PLUMBING PLANA REVIEWER.
  
 3)- FL BLD CODE 4.17.3 TOLIET STALLS/
 LADIES RESTROOM, THE DOOR IS NOT TO
 SWING INTO THE CLEAR FLOOR SPACE SEE
 FIG. 30-E.
  
 4)- FL BLD CODE CHAPTER 11. DISPROPOR-
 TIONATE COST, DEPENDING ON THE RESULTS
 OF COMMENT #2 THE EXISTING RESTROOMS
 MAY NEED TO INCREASE IN WIDTH. 4.1.6.2.2
 DEALS WITH THE 20% DISPROPORTIONATE COST
 INDICATE WHERE THE 20%,TO INCREASE THE
 ACCESSIBLE ROUTE SHALL BE USED, SEE
 ACCESSIBLE ENTRANCE, ACCESSIBLE ROUTE
 THEN RESTROOMS ETC.
 (B)(II) A SERIES OF SMALLER ALTERATIONS
 MAY BE CONSIDERED, THE TOTAL COST OF ALL
 ALTERATIONS WITHIN THE PRECEEDING THREE
 YEARPERIOD SHALL BE CONSIDERED IN DETER-
 MINING WHETHER THE COST OF MAKING THAT
 PATH OF TRAVEL ACCESSIBLE IS DISSPROPOR-
 TIONATE.
  
 5)- FL BLD CODE 1511.7 ROOF MOUNTED
 MECHANICAL UNITS ON RAISED EQUIMENT
 SUPPORTSPROVIDE A MINIMUM CLEARENCE
 HEIGTH IN ACCORDANCE WITH TABLE 1511.7
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096X8412