2002-04-23 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT # 02040691 |
| 423 4TH ST |
| SISCA CONSTRUCTION |
| TEL: 686-9538 |
| |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| 1)- EXISTING RATED STAIRWAY LEADING |
| THROUGH THE EXISTING VESYIBLE, AS INDICA |
| TED ON THE FLOOR PLAN THIS IS THE ONLY |
| AREA THAT REQUIRES A 1 HR FIRE RATING, |
| FL BLD CODE 704.2.4 REQUIRES CORRIDORS |
| EXIT ENCLOSURES AND FIRE RATED WALLS |
| REQUIRED TO HAVE PROTECTED OPENINGS |
| SHALL BE EFFECTIVELY AND PERMANENTLY |
| WITH SIGN OR STENCILING, FIRE WALL & |
| SMOKE BARRIER PROTECT ALL OPENINGS. |
| |
| 2)- FL BLD CODE 104.2.1.2 ADDITIONAL |
| DATA REQUIRED, THE HANDICAPPED RESTROOMS |
| ARE NOT DIMENSIONED, PLEASE PROVIDE THIS |
| ADDTIONAL INFORMATION. THE MINIMUM DIS- |
| TANCE BETWEEN FIXTURES SHALL BE GIVEN BY |
| THE PLUMBING PLANA REVIEWER. |
| |
| 3)- FL BLD CODE 4.17.3 TOLIET STALLS/ |
| LADIES RESTROOM, THE DOOR IS NOT TO |
| SWING INTO THE CLEAR FLOOR SPACE SEE |
| FIG. 30-E. |
| |
| 4)- FL BLD CODE CHAPTER 11. DISPROPOR- |
| TIONATE COST, DEPENDING ON THE RESULTS |
| OF COMMENT #2 THE EXISTING RESTROOMS |
| MAY NEED TO INCREASE IN WIDTH. 4.1.6.2.2 |
| DEALS WITH THE 20% DISPROPORTIONATE COST |
| INDICATE WHERE THE 20%,TO INCREASE THE |
| ACCESSIBLE ROUTE SHALL BE USED, SEE |
| ACCESSIBLE ENTRANCE, ACCESSIBLE ROUTE |
| THEN RESTROOMS ETC. |
| (B)(II) A SERIES OF SMALLER ALTERATIONS |
| MAY BE CONSIDERED, THE TOTAL COST OF ALL |
| ALTERATIONS WITHIN THE PRECEEDING THREE |
| YEARPERIOD SHALL BE CONSIDERED IN DETER- |
| MINING WHETHER THE COST OF MAKING THAT |
| PATH OF TRAVEL ACCESSIBLE IS DISSPROPOR- |
| TIONATE. |
| |
| 5)- FL BLD CODE 1511.7 ROOF MOUNTED |
| MECHANICAL UNITS ON RAISED EQUIMENT |
| SUPPORTSPROVIDE A MINIMUM CLEARENCE |
| HEIGTH IN ACCORDANCE WITH TABLE 1511.7 |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| (561)659-8096X8412 |