2002-04-23 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT # 02040593 |
| 632 HIBISCUS STREET |
| |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| 1)- FLBLD CODE 1606.1.7 INFORMATION |
| ON DRAWINGS, MINIMUM INFO REQUIRED FOR |
| WIND. |
| |
| 2)- SHEET A-1.02 INDICATES NEW DOOR |
| OPENINGS ON THE BACK EXTERIOR OF THE |
| BUILDING. (COMPONENTS & CLADDING) |
| FL BLD CODE 1707.4 EXTERIOR WINDOW & |
| DOOR ASSEMBLIES, PROVIDE PRODUCT APPROV- |
| ALS FOR NEW DOOR OPENINGS, SBCCI OR DADE |
| COUNTY PRODUCT TESTING REPORT.2 COPIES. |
| |
| 3)- FL BLD CODE 1707.4.4 ANCHORAGE |
| METHOD, THIS APPLIES TO WINDOWS & DOOR |
| ASSEMBLIES THAT FASTEN TO THE MAIN FORCE |
| RESISTING SYSTEM. MISSING FASTENER AND |
| FREQUENCY? |
| |
| 4)- FL BLD CODE 104.2.1.2 ADDITIONAL |
| DATA REQUIRED, IS THE STOREFRONT |
| SYSTEM AN EXISTING SYSTEM? OR IS THIS |
| NEW WORK? IF NEW WORK THE SAME PRODUCT |
| TESTING REPORT SHALL BE REQUIRED. |
| IF NEW WORK, LARGE MISSLE IMPACT TESTING |
| SHALL APPLY, IMPACT GLAZING OR SHUTTERS |
| |
| 5)- PROVIDE THE POSITVIE & NEGATIVE |
| PRESSURS THAT APPLY TO THESE OPENINGS |
| BEING AFFECTED. |
| |
| 6)- SHEET A-1.01 DETAILS 1,2 & 4 PLEASE |
| PROVIDE THE UL RATING FOR THE ASSEMBLIES |
| WHERE A 1 HR RATING IS ACHIEVED WITH |
| DRYWALL ON 1 SIDE, WHEN NEXT TO STRUCTUR |
| AL COLUMN W/ FOAM SPRAY APPLIED. |
| |
| 7)- FL BLD CODE 1909.3 CONCRETE SLABS |
| ON GRADE, (2) CONCRETE SLABS ON GRADE |
| CONTAINING 6X6 W1.4XW1.4 WELDED WIRE REI |
| NFORCEMENT FABRIC LOCATED IN THE MIDDLE |
| TO UPPER 1/3RD OF THE SLAB SHALL HAVE |
| APPROVED MATERIALS OR SUPPORTS AT SPAC- |
| ING NOT TO EXCEED 3 FT OR IN ACCORDANCE |
| WITH THE MANUFACTURERS SPEC. |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| (561)659-8096X8412 |
| |
| THIS IS FOR THE SLAB, STEEL FRAMING, |
| DEMISING |