Plan Review Notes For Permit 02040581 |
Permit Number |
02040581 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-04-16 00:00:00 | PROVISO: | | | | 1.PER 2001 FBC 1503.4.4,CONDENSATE | | SHALL TERMINATE A MINIMUM OF 12 IN | | FROM BUILDING STRUCTURE. | | | | 2.2001 FBC, MECHANICAL 601.4, TO AVOID | | PRESSURE DIFFERENTIALS ACROSSED | | CLOSED DOORS WHERE RETURNS ARE | | CENTRALLY LOCATED, PROVIDE AIR DUCT | | PATHWAYS OR AIR TRANSFER PATHWAYS | | FROM THE HIGH PRESSURE ZONE TO THE | | LOW ZONE. | | | | 3.BALANCING DAMPERS OR OTHER MEANS OF | | SUPPLY AIR ADJUSTMENT SHALL BE | | PROVIDED IN THE BRANCH DUCTS OR AT | | EACH INDIVIDUAL DUCT REGISTER, | | GRILLE OR DIFFUSER. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|