Plan Review Notes
Plan Review Notes For Permit 02040581
Permit Number 02040581
Review Stop E
Sequence Number 1
Notes
Date Text
2002-04-11 00:00:00*****************UNSAT!*****************
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} PLEASE SHOW MEANS OF DISCONNECT
 FOR A/C EQUIPMENT PER 440-14.
  
 3} SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52,(DEN).
  
 4} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 5} PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE. PER 210-12
  
 6} PLEASE NOTE KITCHEN COUNTER
 RECEPT TO COMPLY WITH 210-8(A)(6).
  
 7} SMOKE DETECTORS TO COMPLY WITH 2-5.2.
 1.6 NFPA-72.PLEASE MOVE THE ONE IN THE
 WEST BEDROOM TO THE NORTH TO AVOID A
 "NUISANCE" ALARM,ESPECIALLY FROM THE
 KITCHEN AREA.
  
 PLEASE MAKE THE NECESSARY CORRECTIONS
 AND RESUBMIT FOR REVIEW.
  
  