2002-07-31 00:00:00************BUILDING PROVISO************
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE STRUCTURE IS LOCATED IN AN "A8"
 FLOOD ZONE AN ELEVATION CERTIFICATE WILL
 BE REQUIRED.
  
 3) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 SUBMIT (2) COPIES OF A SOIL BEARING TEST
 PRIOR TO POURING THE FOUNDATION.
  
 4)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 EVALUATIONS FOR GLASS BLOCK. ONLY PART
 OF THE METRO-DADE PRODUCT APPROVAL WAS
 SUBMITTED.
  
 5) SUBMIT (2) COPIES OF STORM PANEL
 INSTALLATION SCHEDULES LISTING ALL OF
 THE OPENINGS THAT ARE BEING SHUTTERED.
 THE ONES THAT WERE SUBMITTED LISTED ONLY
 7 OF 10 OPENINGS.