2002-04-19 00:00:00 | **************** UNSAT *************** | | | | 1)NOTE: PLEASE NOTE THAT THE CODES ARTS | | REFERENCED ON PLANS ARE STILL SHOWN | | FROM THE 96 NEC. PLEASE CORRECT AND | | CORRELATE WITH THE 99 NEC. | | | | 2 )NOTE: PLEASE CLARIFY EQUIPMENT | | GROUNDING METHOD BETWEEN FIRST MEANS | | OF DISCONNECT AND PANELS. PLEASE SIZE | | CONDUCTORS PER 250-122. | | | | 3 )NOTE: PLEASE LIST THE REQ`D ARC | | FAULT PROECTED CIRCUITS ON PANEL | | SCHEDULE. PER 210-12 | | | | PLEASE NOTE THAT AIC RATING IS BEING | | SHOWN AS 22.00. MUST BE A MISPRINT. | | THIS IS JUST A NOTE SINCEPLANS ARE | | COMING BACK FOR CORRECTIONS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE NAY QUESTIONS, | | PLEASE CALL.' | | ' | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|