Plan Review Notes
Plan Review Notes For Permit 02040527
Permit Number 02040527
Review Stop E
Sequence Number 1
Notes
Date Text
2002-04-19 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT THE CODES ARTS
 REFERENCED ON PLANS ARE STILL SHOWN
 FROM THE 96 NEC. PLEASE CORRECT AND
 CORRELATE WITH THE 99 NEC.
  
 2 )NOTE: PLEASE CLARIFY EQUIPMENT
 GROUNDING METHOD BETWEEN FIRST MEANS
 OF DISCONNECT AND PANELS. PLEASE SIZE
 CONDUCTORS PER 250-122.
  
 3 )NOTE: PLEASE LIST THE REQ`D ARC
 FAULT PROECTED CIRCUITS ON PANEL
 SCHEDULE. PER 210-12
  
 PLEASE NOTE THAT AIC RATING IS BEING
 SHOWN AS 22.00. MUST BE A MISPRINT.
 THIS IS JUST A NOTE SINCEPLANS ARE
 COMING BACK FOR CORRECTIONS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE NAY QUESTIONS,
 PLEASE CALL.'
 '
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372