2002-04-26 00:00:00 | **************** NOTE ************* | | | | 1)NOTE: PLEASE NOTE THAT THE CODE ARTS | | ARE STILL FROM THE 96 NEC, PLEASE | | CORRELATE W/ 99 NEC. | | | | 2)NOTE: PLEASE NOTE MISPRINT FOR AIC | | RATING, SHOWN AS 22.00, SHOULD SHOW AS | | 22,000. | | | | 3))NOTE: PLEASE CLARIFY EQUIPMENT | | GROUNDING METHOD BETWEEN FIRST MEANS | | OF DISCONNECT AND PANELS. PLEASE SIZE | | CONDUCTORS PER 250-122. | | | | | | 4 )NOTE: PLEASE LIST THE REQ`D ARC | | FAULT PROTECTED CIRCUITS ON PANEL | | SCHEDULE OR NOTES. PER 210-12 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|